Configuration 14 - Allen-Bradley Guardmaster GuardLink User Manual

Safety system
Table of Contents

Advertisement

Appendix B
Configuration Examples
Configuration 5
Figure 73 - One Safety Input, Middle SWS, Automatic Reset Assigned to Safety Outputs
Schematic
+24V DC
Test Out
A1
S11
S21
GSR
DG
CI/SI/DI/DIS
440R-DG2R2T
A2
L12 L11
S32
S42
IN X
24V DC Com
100
In Configuration 5, only safety Input 1 is in use. It can either be configured for
GuardLink or OSSD with autodetect of EMSS devices. Input devices are not
shown in the drawing.
The input IN X (terminal X1) is configured for SWS In. This input is ANDed
with IN 1.
The output OUT X (terminal X2) is configured for SWS Out and can drive
any other SWS compatible device. In this example, the SWS out is driving an
EM safety relay. OUT X is switched off immediately when demanded by the
safety functions. The relay outputs 14/24 can be configured for a time delay to
switch off after the delay time.
The relay configuration is considered a middle SWS as it requires an SWS
input and provides an SWS output.
The Reset mode is configured for automatic/manual and assigned to the safety
outputs. After a demand of the safety function by any input, the outputs are
enabled when all safety inputs are ACTIVE and the feedback signal is present.
A reset operation is not required.
Input 1
A1
S12
S22
A1
13 23
X4
TIME
EM
440R-EM4R2
A2
L12
X1
X2
A2
14
24
X3
OUT X
SWS
K1
K2
Table 33 - Configuration 5
Indicator
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
K1
X32
13 23 33 43
K2
K3
L11
14 24
34
44
K4
Feedback
K3
K4
Function
Configuration ID: 0x1A
Safety Functions
IN1
Input Type
GuardLink
Input Type
Not used
Output Type
SWS
Input Mode
SWS Enabled
Reset Type
Automatic
Reset Assignment
Not used
Logic
IN X
IN 1
SMF Level
&
LOGIC Level
SOF Level
FB
OUT X
OUT 14/24
Configuration ID: 0x18
IN1
OSSD/EMSS
Not used
SWS
SWS Enabled
Automatic
Not used