SULFURIC ACID WARNING
The batteries contain sulfuric acid, which can cause severe burns to the skin and eyes and can
destroy fabric. Replace any leaking or damaged battery while wearing appropriate protective gear.
If you come in contact with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES
To ensure proper system operation, this product must be tested in accordance with AS 1670.1
after any programming operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions, known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, should also be tested and proper system operation verified.
SOFTWARE VERSION COMPATIBILITY
Verify 4100ESi System Programmer, Executive, and Slave Software compatibility when installing
or replacing system components. Refer to the Solutions Bulletin SB11002 for more information.