Connecting and commissioning

8.6 Final settings and checks

8.6
Final settings and checks
Final settings
1. Activate the application-specific relay module functionalities. (Optional, only for control
devices with a relay module)
Proceed as described in the section Relay module (Page 54).
2. Configure the connected sensor type.
3. Switch on the control device by connecting the power supply to the control device and to
the network.
The four LEDs alongside the plug connector X6 indicate which control signal is currently
active. If input 1 is configured as a light barrier input and there is no obstacle in the travel
direction, the LED for light barrier/DCPS input lights up continuously.
If the control signal CLOSE is present, the door moves into the CLOSED position at initial
speed.
If an OPEN control signal is set, the door moves into the OPEN position at initial speed.
The OPEN signal has priority over the CLOSE signal!
Once the controller has detected the door OPEN and CLOSED end positions, the
subsequent opening and closing movements proceed at normal speed once again.
Note
An opening or closing command must be present until the entire travel distance from OPEN
to CLOSE or from CLOSE to OPEN can be completely traversed and the doors dwells for an
additional second in the OPEN and CLOSE door position.
132
Door control units SIDOOR AT40 and ATD400V for elevators
System Manual, 06/2018, A5E42192709-AC