4.5 Relay and field bus interfaces
Terminal circuit diagram of the relay contacts
Procedure
Note
Specifications for connecting the relay module
• The cables connected must be suitable for the voltage used and have appropriate
(double or reinforced) insulation. Cables with an external diameter of 6 to 7 mm are
recommended.
• Components of the control device and connecting cable, such as the motor plug and its
wires, may only come in contact with the additional (or reinforced) insulation of the
current-carrying wires.
• Networks with different voltages (for example 24 V and 230 V) must not be connected to
the relay module.
56
Cable ties (strain relief in enclosure)
Cable ties (security against being pulled out within the protective cover)
Minimum length of the cable jacket within the protective cover: 5 mm
Minimum length of the single-insulation on the single cores: 5 mm
Insertion direction for the protective cover
Door control units SIDOOR AT40 and ATD400V for elevators
System Manual, 06/2018, A5E42192709-AC