1. Unscrew the fixing screw holding the protective cover on the relay module.
2. Slide the protective cover against the insertion direction and remove it.
3. Connect connectors X11, X12 and X13.
4. Ensure that the single-insulation inside the cover is removed from the single cores at
least 5 mm from the cable entry openings, and the wires connected to the terminal
connectors are as short as possible.
5. Secure the cables inside the plastic cover against being pulled out through the oval
aperture in the relay cover. Use cable ties for this purpose, tie each of them tightly round
the cable.
Ensure that the cable tie is tied so that at least 5 mm of the outer cable jacket lies inside
the protective cover.
6. Provide additional strain relief by attaching more cable ties to the fixing points provided in
the enclosure.
7. Slide the protective cover in the insertion direction back into its correct position.
8. Screw the fixing screw holding the protective cover on the relay module back in.
Door control units SIDOOR AT40 and ATD400V for elevators
System Manual, 06/2018, A5E42192709-AC