Battery Test - Sanyo Denki SANUPS E11A102U-J Instruction Manual

E11a series 1kva, 2kva, 3kva 200v model hybrid ups type c
Hide thumbs Also See for SANUPS E11A102U-J:
Table of Contents

Advertisement

§
1
3
.
2
B
a
t
t
e
r
y
§
1
3
.
2
B
a
t
t
e
r
y
You can perform tests of the built-in and externally connected batteries. You can do this without stopping the
load devices connected to the UPS.
When it is shipped from the factory, the UPS is set up to perform an automatic battery test once every 180
days. To change the automatic battery test schedule, see §3.5 "Setting Test Schedule" in the
Guide
.
Follow the procedure below when conducting a manual battery test. However, if the UPS has performed a
backup operation within 12 hours prior to the test, the result may show an error. The test should, therefore,
be conducted when the UPS has not performed a backup operation within the last 12 hours.
① Press
and hold it for at least 2 seconds.
The "Green BATT. TEST" indicator starts blinking, and the battery test starts.
Buzzer
2 beeps... 2 beeps... 2 beeps...
LED
Green BATT. TEST Blinking
Battery operation for approx.
90 seconds
The test finishes
in approx. 90 seconds.
Check the "Green BATT. TEST" indicator for the results of the test.
Battery Test Results
② After the battery test has finished and the "Green BATT. TEST" indicator lights
or blinking, press
The "Green BATT. TEST" indicator goes off and returns to its normal indication.
Note for the battery test
The results of the test are only an approximate guide. If the batteries have reached their replacement
interval, an early replacement is recommended even if the results of the test are OK. See "Estimated battery
replacement interval" in the previous page for more information.
Condition for battery test
Battery test cannot be performed under the following conditions.
1. Inverter is stopped.
2. Bypass power supply is active.
3. Input voltage or input frequency is out of range.
Stopping battery test
To stop the battery test while it is underway,
Press
for at least 2 seconds
The battery test stops if any of the following 1-4 occur or if any of the following 5-8 is operated while it is
underway.
1. Input power error (voltage or frequency).
2. Mechanical failure
3. Output power overload
4. If the load level will be less than 20% when the UPS
operates in Active Filter Mode or Economy Mode.
The "Green BATT.TEST" indicator does not display the results of the test if the test is interrupted.
T
e
s
t
T
e
s
t
Green BATT. TEST
Buzzer
Confirmed
90 seconds
Backup Time
or more
The batteries
Result
are OK.
.
The UPS returns to normal operation.
lit
******* 7 beeps ... ******* 7 beeps ....
Less than 90 seconds
Replacing the battery early is recommended.
Contact SANYO DENKI.
4. Shutdown under remote control is in progress.
5. UPS is defective.
6. When load factor is less than 20% in the economy mode
operation or the active filter mode operation.
5. Switching of
Forced Bypass
6. Setting
MAIN MCCB
7. Pressing
8. Executing the battery test stop by the power
control software
Maintenance
User Settings
Hold for 2 seconds.
blink
switch
to "OFF"
for 1 second or longer
40