12. Special Functions

◆ 12.1 Battery Test
The battery backup time test checks whether the batteries are able to operate the
existing load during a power outage. The test is performed without interrupting the load.
We recommend that batteries be tested once every three months. The test should be
performed after the batteries have been allowed to charge for at least 12 hours.
However, if the P.R.O. LED is off, the battery test cannot be performed.
① On any UPS Unit (which one does not matter), press
seconds.
UPS status
Beeper sound: Beep beep・・・beep beep・・
・beep beep・・・
BATT.TEST (green) blinks
Battery operation for about two min.
All of the green BATT. TEST LEDs blink,
as testing of all batteries starts at once
The test finishes after about two minutes, then normal operation resumes with results
indicated by the LEDs on each UPS Unit.
However, if an abnormal UPS Unit is found, testing of the other UPS Unit(s) is aborted.
Battery Test Results
Indication
Lit
Long blinking
Off
② If necessary, press
Normal operation resumes.
③ When finished the test and after verifying battery test results, press
all UPS Units.
The LEDs turn off.
The battery test aborts if one of the following conditions occurs:
① Abnormal AC input (voltage, frequency)
② Fault
③ Bypass switch change
④ Output overload
⑤ INV ON/STAND BY
⑥ When any UPS Unit is abnormal
Note
This test provides only rough information. Even if the test results indicate normal battery
condition, please contact your service representative when the battery expiration date is
near.
Backup confirmation time
more than 2 min.
less than 2 min.
BATT.TEST to abort the battery test.
is OFF.
- 29 -
BATT.TEST for at least two
Hold for at least 2
seconds.
Judgment
Batteries are normal.
Replace batteries soon.
Battery test aborted.
CLEAR
on