When installing the UPS, carefully follow the instructions in
this Instruction Manual. Improper installation can result in
electric shock, bodily injury, and/or fire.
Install the UPS on a stable surface that can bear the weight
(see the table). This surface should be flat, so the UPS cannot
fall and cause bodily injury. The possibility of vibration and
shock should be minimized at the installation location.
All work that involves lifting the UPS, such as mounting it in a rack or attaching the
CAUTION
stand, should be carried out by at least 2 persons. For safety, put on protective shoes.
Be careful to avoid straining your lower back when moving and installing the UPS.
There is a danger that the UPS could fall or be dropped during relocation or installation.
Always hold the bottom side of the UPS firmly with both hands. Failure to do so can
result in bodily injury or damage to the UPS.
§
6
.
1
I
n
s
t
a
l
l
a
t
i
§
6
.
1
I
n
s
t
a
l
l
a
t
i
Suitable installation environment:
Ambient temperature: 0 to 40°C (32 to 104°F)
Relative humidity: 20 to 90%
Do not install the UPS in the following locations:
Where the ambient temperature exceeds 40°C (104°F).
Where high humidity may occur.
Where corrosive gas or salt spray may be present.
Where it may be subject to vibration and shock.
Where dust may accumulate.
When the UPS is rack mounted, in a poorly ventilated rack.
§
6
.
2
I
n
s
t
a
l
l
a
t
i
§
6
.
2
I
n
s
t
a
l
l
a
t
i
During installation, provide the following space around the UPS.
At least 20 cm (8 inches) at the front and back as air intake or exhaust space for cooling.
At least 1 meter (40 inches) from CRT displays to allow for slight leakage of magnetic flux.
Allow some space from devices which might be affected by magnetic flux.
At least 20cm(8 inches)
Note for installation
For maintenance of the UPS allow for the space at least 1 meter (40 inches) at the front and 50 cm
(20 inches) at the back when needed.
a
t
i
o
n
a
t
i
o
n
o
n
E
n
v
i
r
o
n
m
e
n
o
n
E
n
v
i
r
o
n
m
e
n
o
n
S
p
a
c
e
C
h
e
c
k
o
n
S
p
a
c
e
C
h
e
c
k
Back
At least 20cm(8 inches)
t
C
h
e
c
k
t
C
h
e
c
k
Note
Battery service life will be foreshortened if the
UPS is used in an environment where the
ambient temperature exceeds 30°C (86°F).
For optimum battery life, install the UPS
where the ambient temperature remains
between 20 to 25°C (68 to 77°F).
Back At least 1m(40in.)
Front

Installation

Weight
Model
kg
lbs
E11A102
17
37.5
E11A202
29
63.9
E11A302
39
85.9