Load Devices Connection - Sanyo Denki SANUPS E11A102U-J Instruction Manual

E11a series 1kva, 2kva, 3kva 200v model hybrid ups type c
Hide thumbs Also See for SANUPS E11A102U-J:
Table of Contents

Advertisement

§
1
0
.
L
o
a
d
§
1
0
.
L
o
a
d
Connect the load devices.
① Attach the supplied cable clamps to the input
power plug of the load device to be connected.
② Check that the input breaker
③ Connect the input power plugs of the load devices to the output terminals.
② Breaker is "OFF".
The cable clamp cannot be
removed once it is inserted.
Loosen it as shown below if
you need to disconnect the
input power cable.
Model
The total load connected to the receptacles
must not exceed
AC250V 15A receptacle
E11A102
IEC60320- C13 × 4
The total load connected to the receptacles
must not exceed
E11A202
AC250V 20A receptacle
IEC60320- C19 × 3
The total load connected to the receptacles
must not exceed
AC250V 20A receptacle
E11A302
IEC60320- C19 × 3
Notes for proper load device connections
Connect as shown below, according to the type of grounding in the area where you are installing the UPS.
Areas which do not have single-line grounding:
connect the W (N) terminal of the load device input plug to the N terminal of the UPS. (See the above figure.)
Areas which have single-line grounding:
connect the ground phase to the N terminal (phase) side. (See the above figure.)
Never connect the following types of load devices to the UPS.
Load devices
Copy machines, Laser printers,
Plain paper fax machines,
Overhead projectors, Hair-dryer, Cleaner
and so on.
Medical equipment, control equipment for
elevators and the like, computer systems
of public importance.
D
e
v
i
c
e
s
C
D
e
v
i
c
e
s
C
MAIN MCCB is set to "OFF".
Press the tab.
Outlet Capacity
1.0kVA (0.7kW)
.
2.0kVA (1.4 kW)
.
3.0kVA (2.1kW)
.
If the load devices are a single-wire grounded connection, always
Since such devices are subject to high transient current
surges, the UPS will detect the excess current and
backup will not be possible when there is a power
outage. There is also the risk of the UPS malfunctioning.
Special considerations such as system redundancy,
installation of emergency power generation facilities,
need to be given to operation, maintenance, and
management.
This completes the load devices connection.
o
n
n
e
c
t
i
o
n
o
n
n
e
c
t
i
o
n
Attach the cable clamp to
the input plug of the load.
③ Insert the cable clamp into the hole, and
then connect the input power cable of the
load device.
Do not strain the cable clamp too tightly.
If the load device input plug is a NEMA-type plug,
Details

Load devices connection

Receptacle
N
L
E
30