Ups Charge - Sanyo Denki SANUPS E11A102U-J Instruction Manual

E11a series 1kva, 2kva, 3kva 200v model hybrid ups type c
Hide thumbs Also See for SANUPS E11A102U-J:
Table of Contents

Advertisement

Preparation Before Operation
§
9
.
2
U
P
§
9
.
2
U
P
At initial startup or when the UPS is not operated
for long period, the UPS should be charged for at
least 12 hours before operation.
Proceed as follows before connecting the load devices.
① Set
② Check that the alarm buzzer (7 beeps, pose, 7 beeps, pose...)
does not sound.
If the alarm buzzer sounds, the battery connector inside the front panel might not be connected.
Set
connection". After connecting the battery connector, proceed to step 1 again. If the alarm buzzer
sounds again, contact your supplier or a SANYO DENKI representative.
③ Check that the "Green INPUT" stops blinking and remains lit.
Charging of the UPS starts automatically.
④ Operate the UPS for at least 12 hours in this state.
Note on the charging time
The UPS should be charged for at least 12 hours to ensure backup in the event of a power outage, but
load devices can be connected for use when the UPS is first activated even if there is insufficient charge
because the battery will be charged during operation of the UPS. However, if a power outage occurs at
that stage, the full capacity of the backup function may not be available.
* The UPS should be charged as follows when the battery modules (optional) are connected.
20-minute backup
Battery module f
30-minute backup
Battery module f
27
S
C
h
a
r
g
e
S
C
h
a
r
g
e
MAIN MCCB on the back panel of the UPS to "ON".
Set to "ON".
to "OFF", then connect the battery connector. See §7.1 "Battery connector
MAIN MCCB
Battery module
Connected UPS
Type
E11A102
or E11A
E11A202
E11A302
or E11A
This completes the charging of the UPS.
Indications of Switch and LED in this manual.
The switches or breakers are indicated by a frame
Example:
MAIN MCCB
The LEDs on the control panel are described as
"Green INPUT" or "Red ALARM".
The LEDs state are indicated as follows;
: LED lights.
Connecting unit qty.
Backup time
1
20 min.
2
40 min.
3
60 min.
1
30 min.
2
60 min.
.
: LED blinks.
LEDs
Green INPUT
Blinking
Green INV.ON/STAND BY Off
Green OUTPUT
Off
Green INPUT
Lit
Green INV.ON/STAND BY Off
Green OUTPUT
Off
Charge time
At least 36 hours
At least
hours
60
At least
hours
84
At least
hours
48
At least
hours
84
.