The buzzer sounds to indicate an UPS status error or change.
Check the sound pattern and refer to the following table for the steps to take.
Sound Pattern
Continuous tone
*
2 seconds
**
** ...
2 beeps
2 beeps
Continuous beeps
******************* ・・・
3 seconds
* * * *
* * * * ・・・
4 beeps
4 beeps
2 seconds
* * * * * * *
* * * * * * *・・
7 beeps
7 beeps
2 seconds
* * * * *
* * * * * ・・・
5 beeps
5 beeps
Note
Contact your supplier if any other failure occurs in the UPS.
r
S
o
u
n
d
s
e
r
S
o
u
n
d
s
LED Status
UPS Status
This is a mechanical
Red ALARM lit
failure.
【When UPS starts】
【During bypass operation】
Red ALARM lit
The bypass breaker tripped
or is set to "OFF".
Red ALARM lit
Red BATT.LOW
The battery is exhausted.
lit
Power is being supplied
Green INPUT
from the battery because of
an input voltage or
blinking
frequency error.
MAIN MCCB
Green INPUT
to "OFF" during UPS
blinking
power supply.
Green
The UPS is performing
BATT.TEST
a battery check.
blinking
Red BATT.LOW
The battery voltage is low.
lit
The load devices connected
to the output terminal
Red O.L lit
exceed the rated capacity
of the UPS.
【When UPS starts】
The battery connectors are
Green
not connected.
BATT.TEST
blinking
The battery check result
was an error.
Remaining battery
-
service life is six months.
Red BATT.LOW
The battery has reached
blinking
its service life.
Contact your supplier.
Reset the bypass breaker, see §13.3 "Bypass
Breaker Reset".
And when using E11A302, see step 3 in §7.3
"Input Plug Connection".
When utility power is restored, the UPS will
restart automatically depending on the setting
value of "UPS Operation Upon Power
Recovery" in the user setting. See §3.7 "Setting
UPS Operation Upon Power Recovery" in the
User Settings Guide.
Verify that the input voltage and input
frequency are within the rated range. Refer to
§19.4 "Specifications".
was set
Set MAIN MCCB
Wait for the battery check to end. You can stop
the battery check by pressing
it for at least 2 seconds.
Verify that the input voltage and input
frequency are within the rated range. Refer
to §19.4 "Specifications".
MAIN MCCB
MAIN MCCB
Connect fewer load devices to the output
terminal.
Stop the UPS, refer to §7.1 "Battery Connector
Connection", and firmly connect the battery
connectors.
After connecting the battery connectors, start
the UPS, and check to make sure that buzzer
sounds are not head and that "Green
BATT.TEST" does not blink.
Perform the battery test. Refer to §13.2
"Battery Test". When the same result persists,
the battery must be replaced. Contact your
supplier.
A battery replacement is recommended.
Contact your supplier.
You can press
But the buzzer sound will start again the next
time the UPS is powered on. This will continue
until you replace the battery.
The battery must be replaced. Contact your
supplier.
You can press
"Red BATT. LOW" blinking continues.
The buzzer sound and LED blinking will start
again the next time the UPS is powered on.
This will continue until you replace the battery.

Buzzer Sounds

T i p
Press
to stop the buzzer.
What to Do
to "ON".
and holding
may be set to "OFF". If
is "OFF", set it to "ON".
to stop the buzzer sound.
to stop the buzzer sound, but
44