At initial startup or when the UPS is not operated
for long period, the UPS should be charged for at
least 12 hours before operation.
Proceed as follows before connecting the load devices.
① Set
Set to "ON".
② Check that the alarm buzzer (7 beeps, pose, 7 beeps, pose...)
does not sound.
If the alarm buzzer sounds, the battery connector
inside the front panel might be not connected.
Set MAIN SW
connector. See §7.1 "Battery connector connection".
After connecting the battery connector, proceed to step
1 again. If the alarm buzzer sounds again, contact
your supplier or SANYO DENKI representative.
③ Check that the "Green INPUT" stops blinking and remains lit.
Charging of the UPS starts automatically.
④ Operate the UPS for at least 12 hours in this state.
Note on the charging time
The UPS should be charged for at least 12 hours to ensure backup in the event of a power outage, but
load devices can be connected for use when the UPS is first activated even if there is insufficient charge
because the battery will be charged during operation of the UPS. However, if a power outage occurs at
that stage, the full capacity of the backup function may not be available.
* The UPS should be charged as follows when the battery modules (optional) are connected.
15-minute backup
Battery module for E11A
20-minute backup
Battery module for E11A
30-minute backup
Battery module for E11A
23
S
C
h
a
r
g
e
S
C
h
a
r
g
e
MAIN SW on the back panel of the UPS to "ON".
OUTPUT max.700W 10A
MAIN SW
EXT.
EXT.
BATT
BATT
to "OFF", then connect the battery
Battery module
Connected UPS
Type
E11A302
E11A102
E11A152
E11A202
This completes the charging of the UPS.
Indications of Switch and LED in this manual.
The switches or breakers are indicated by a frame
Example:
The LEDs on the control panel are described as
"Green INPUT" or "Red ALARM".
The LEDs state are indicated as follows;
: LED lights.
INPUT
Connecting unit qty.
Backup time
1
15 min.
2
30 min.
3
45 min.
1
20 min.
2
40 min.
3
60 min.
1
30 min.
2
60 min.
MAIN SW .
: LED blinks.
LEDs
Green INPUT
Green INV.ON/STAND BY Off
Green OUTPUT
Green INPUT
Green INV.ON/STAND BY Off
Green OUTPUT
Note for E11A302
Only when using E11A302;
if the alarm buzzer (continuous tone) sounds when
turning on
,
MAIN MCCB
BYPASS OC 30A
be "OFF". Set
to "OFF" once, perform
MAIN MCCB
steps 1 to 3 described in §7.2 "Input Plug
Connection" again.
Charge time
At least 36 hours
At least 60 hours
At least 84 hours
At least 36 hours
At least 60 hours
At least 84 hours
At least 48 hours
At least 84 hours
.