Installation

3.3 EMC Precautions

To achieve interference-free operation of the DeviceNet:
Maintain high distance (min. 200 mm [8"])
between the DeviceNet communication cable and
3
3
the motor and brake resistor cables to avoid
coupling of high frequency noise from one cable
to the other.
When crossing is unavoidable, ensure that the
DeviceNet cable crosses motor and brake resistor
cables at an angle of 90°.
NOTICE
Observe relevant national and local regulations, for
example regarding protective earth connection.
Min.200mm
90° crossing
Illustration 3.4 Correct EMC Installation
10
Operating Instructions
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
MG37E102