Parameter Mapping Lists
VLT 5000 series
Parameter 205 Maximum
reference
Range
Par. 204 Ref
100,000.000
5
5
Table 5.57 Conversion of Parameter 205
VLT 5000 series
Parameter 206 Ramp Type
Options
[0] Linear
[1] Sine shape (S1) Par. 3-40 = [2] S-ramp Const Time
[2] Sin2 Shape
(S2)
Table 5.58 Conversion of Parameter 206
20
Operating Instructions
FC 302 series
3-03 Maximum Reference
6-15 Terminal 53 High Ref./Feedb.
Value
6-25 Terminal 54 High Ref./Feedb.
Value
5-53 Term. 29 High Ref./Feedb.
Value
5-58 Term. 33 High Ref./Feedb.
Value
–
Par. 3-02 Ref
– 100,000.000
min
min
FC 302 series
3-40 Ramp 1 Type
3-50 Ramp 2 Type
3-82 Quick Stop Ramp Type
Par. 3-40 = [0] Linear
Par. 3-50 = [0] Linear
Par. 3-82 = [0] Linear
Par. 3-45 = 1%
Par. 3-46 = 25%
Par. 3-47 = 1%
Par. 3-48 = 25%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 1%
Par. 3-56 = 25%
Par. 3-57 = 1%
Par. 3-58 = 25%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 1%
Par. 3-84 = 25%
Par. 3-40 = [2] S-ramp Const Time
Par. 3-45 = 25%
Par. 3-46 = 25%
Par. 3-47 = 25%
Par. 3-48 = 25%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 25%
Par. 3-56 = 25%
Par. 3-57 = 25%
Par. 3-58 = 25%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 25%
Par. 3-84 = 25%
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
VLT
FC 302 series
5000
series
Parameter 206
3-40 Ramp 1 Type3-50 Ramp 2
Ramp
Type3-82 Quick Stop Ramp Type
Type
Options
[0]
[0] Linear. Write to p.340, 350 and 382
Linear
[3] Sin3
Par. 3-40 = [2] S-ramp Const Time
Shape
Par. 3-45 = 50%
(S3)
Par. 3-46 = 50%
Par. 3-47 = 50%
Par. 3-48 = 50%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 50%
Par. 3-56 = 50%
Par. 3-57 = 50%
Par. 3-58 = 50%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 50%
Par. 3-84 = 50%
[4] Sin2
Par. 3-40 = [2] S-ramp Const Time
filter
Par. 3-45 = 25%
Par. 3-46 = 25%
Par. 3-47 = 25%
Par. 3-48 = 25%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 25%
Par. 3-56 = 25%
Par. 3-57 = 25%
Par. 3-48 = 25%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 25%
Par. 3-84 = 25%
Table 5.59 Conversion of Parameter 206
VLT 5000 series
Parameter 207 Ramp up Time 1
Range
0.05 – 3600.00 s
Table 5.60 Conversion of Parameter 207
VLT 5000 series
Parameter 208 Ramp down Time 1 3-42 Ramp 1 Ramp Down
Range
0.05 – 3600.00 s
Table 5.61 Conversion of Parameter 208
VLT 5000 series
Parameter 209 Ramp up Time 2
Range
0.05 – 3600.00 s
Table 5.62 Conversion of Parameter 209
VLT 5000 series
Parameter 210 Ramp down Time 2 3-52 Ramp 2 Ramp Down
Range
0.05 – 3600.00 s
Table 5.63 Conversion of Parameter 210
FC 302 series
3-41 Ramp 1 Ramp Up Time
0.01 – 3600.00 s
FC 302 series
Time
0.01 – 3600.00 s
FC 302 series
3-51 Ramp 2 Ramp Up Time
0.01 – 3600.00 s
FC 302 series
Time
0.01 – 3600.00 s
MG37E102