User Specific Record Data - Danfoss VACON 100 industrial Installation Manual

Integrated profinet io
Hide thumbs Also See for VACON 100 industrial:
Table of Contents

Advertisement

vacon • 30
Signal no.
137
138
139
5.4.4

User specific record data

For easy access to drive parameters and monitoring values, the VACON
PROFINET user specific record indexes 0x0000 - 0x7FFF directly into the application IDs of the drive
based on the IEC61131 standard. Both read and write access is supported.
NOTE! The response data is in raw format. See application manual for available IDs, amount of
decimals and the unit used for the parameters.
In the examples below, the following index values are used:
• 102 = Maximum frequency (Hz)
• 600 = Motor control mode
AC drive
®
VACON
AC drive
®
VACON
100
5
Table 23. PROFIdrive signal numbers
Signal name
®
VACON
DW PDI6
®
VACON
DW PDI7
®
VACON
DW PDI8
Table 24. Application ID access settings
Slot
Subslot
1
2
Access IDs as VACON® 100 actual data type
Table 25. Example 1: Reading values from the AC drive
Read command
Slot
Subslot
1
2
100
Table 26. Example 2: Writing values for the AC drive
Write command
Slot
Subslot
Index
1
2
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
PNU
10122
VACON
10122
VACON
10122
VACON
Description
Index
Hex
102
00 07 A1 20
600
00 00 00 01
Length
Value (Hex)
102
4
00 06 DD D0
600
4
00 00 00 00
PROFINET IO protocol
PNU name
®
32-bit Process Data In
®
32-bit Process Data In
®
32-bit Process Data In
®
100 AC drive maps the
Response
Dec
Actual value
500000
50.0000 Hz
1
1 = OL Speed
Actual value
45.0000 Hz
0 = OL Frequency

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon 100 flowVacon 100 x