PROFINET IO protocol
5.4.6.3
PROFIdrive Parameter Access errors
In addition to the error indications in the error response field, details about the error are provided
in the parameter value field. The third octet in the parameter value is set to 0x00 and the fourth octet
is assigned the error number, as described in Table 36.
Error number Meaning
Impermissible parameter
0x00
number
Parameter value cannot
0x01
be changed
0x02
0x0 = invalid index
0x03
Invalid subindex
0x04
Non-array parameter
0x05
Incorrect data type
Setting not permitted (may
0x06
only be reset)
Description element can-
0x07
not be changed
0x08
Reserved (not used)
No description data avail-
0x09
able
0x0A
Reserved (not used)
0x0B
No operation priority
0x0C...0x0E
Reserved (not used)
0x0F
No text array available
0x10
Reserved (not used)
Request cannot be exe-
0x11
cuted
0x12...0x13
Reserved (not used)
0x14
Value impermissible
0x15
Response too long
Impermissible parameter
0x16
address
0x17
Illegal format
Number of values are not
0x18
consistent
0x19
Axis non-existent
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Table 36. PROFIdrive parameter access errors
When used
Access to unavailable parameter.
Change request to a read-only parameter.
0xB0 = parameter requests are not supported.
Access to an unavailable subindex of an array pa-
rameter.
Attempt to access subindex of a non-array parame-
ter.
Change request containing invalid data type for the
accessed parameter.
Change request to a non-zero value, where this is
not allowed.
Change request to a read-only parameter descrip-
tion element.
Access to unavailable parameter description.
Change request without access rights to perform
the change.
Access to unavailable parameter text array.
Access is temporarily not possible due to unspeci-
fied reasons.
Change request with a value within the allowed
range, but is otherwise not permissible.
The length of the respose exceeds the maximum
transmittable length.
Error in the parameter address field.
Illegal format was provided in write request.
The number of values in the write request does not
match the number of values in the parameter.
Access to non-existent axis number