Status Word Descriptions

The Status word is composed of 32 bits. FBFixedStatusWord consist of the first 16 bits. FBGen-
eralStatusWord consist of the remaining 16 bits. While the functionality of FBFixedStatusWord is
fixed in the VACON
application specific and can vary even in the VACON
The meanings of FBFixedStatusWord bits are described below. Unused bits have to be set to zero..
Bit
B0
B1
B2
B3
B4
B5
B6
B7
B8-B12
8
®
standard applications, the functionality of FBGeneralStatusWord is totally
Table 51. FBFixedStatusWord bits
Function
Ready
Run
Direction
Fault
Alarm
At reference
Zero speed
Flux ready
Reserved
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
APPENDIX 2 - CONTROL AND STATUS WORD
®
standard applications.
Description
0
Drive is not ready.
1
Drive is ready to run.
0
Motor is not running.
1
Motor is running.
0
Motor is running clockwise.
1
Motor is running counterclockwise.
0
No fault active.
1
Drive has an active fault.
0
No alarm active.
1
Drive has active alarm.
0
Motor is not running at reference speed.
1
Motor is running at reference speed.
0
Motor is not at zero speed.
1
Motor is running at zero speed.
0
Motor is not magnetized.
1
Motor is magnetized.