vacon • 36
5.4.6.2
PROFIdrive 4.1 error classes and codes
The table below lists PROFIdrive profile 4.1 error classes and codes.
Error class
0x0...0x9 = reserved (not used)
0xA = applica-
tion
0xB = access
0xC = resource
0xD...0xF = user-specific (not used)
5
Table 35.
PROFIdrive 4.1 error classes and codes
Error codes
0x0 = read error
0x1 = write error
0x2 = module failure
0x3...0x7 = reserved (not
used)
0x8 = version conflict
0x9 = feature not supported
0xA...0xF = user-specific
(not used)
0x0 = invalid index
0x1 = write length error
0x2 = invalid slot
0x3 = type conflict
0x4 = invalid area
0x5 = state conflict
0x6 = access denied
0x7 = invalid range
0x8 = invalid parameter
0x9 = invalid type
0xA...0xF = user-specific
(not used)
0x0 = read constraint con-
flict
0x1 = write constraint con-
flict
0x2 = resource busy
0x3 = resource unavailable
0x4...0x7 = reserved (not
used)
0x8...0xF = user-specific
(not used)
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
PROFIdrive meaning
0xB0 = parameter requests are not supported.
0xB5 = parameter access is temporarily not possi-
ble due to internal processing status.
0xB7 = Write request with error in the parameter
request header.
PROFINET IO protocol