vacon • 38
Error number Meaning
0x20
0x21
0x22...0x64
0x65
0x66
0x67
0x68
0x69
0x6A
0x6B
0x6C
0x6D
0x6E
0x6F...0xFF
5
Table 36. PROFIdrive parameter access errors
Parameter text cannot be
changed
Invalid request ID
Reserved (not used)
Invalid request reference
Invalid request ID
Reserved (not used)
Invalid number of parame-
ters
Invalid attribute
Reserved (not used)
Request is too short
Parameter not found.
Invalid change request.
General error
Reserved (not used)
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
When used
Change request to unavailable parameter text.
If a parameter request does not have the request ID
01h or 02h, this error code is returned.
Unallowed value for request reference.
Unallowed value in request ID (neither Request Pa-
rameter nor Change Parameter).
Invalid number of parameters in request (0 or
greater than 39).
Invalid attribute specified in request.
Not enough parameter value data was transmitted
in a Change request. Alternatively, the request did
not contain a complete parameter address.
Parameter was not found or error occurred while
accessing it.
Issue with request was found and request was not
handled.
General error occurred.