Name Of Station; Communication Timeout; Ethernet Common Settings - Danfoss VACON 100 industrial Installation Manual

Integrated profinet io
Hide thumbs Also See for VACON 100 industrial:
Table of Contents

Advertisement

vacon • 14
Code
Parameter
Number of process
P5.9.5.2.6
P5.9.5.2.7
Drive control word
P5.9.5.2.8
Drive status word
Connection time-
P5.9.5.2.9
P5.9.5.2.10
Parameter access
P5.9.5.2.11 Profile control word
P5.9.5.2.12 Profile status word
4.2.1

Name of Station

The Profinet IO "Name of Station" parameter can be set via VACON
this name by writing it via Ethernet with the DCP protocol. The name is empty if no name is set, or
if name is set as "temporary" by network device.
4.2.2

Communication timeout

The Communication timeout defines how much time can pass from the last received message from
the Master Device before a fieldbus fault is generated. This value is considered as an additional
timeout which works on top of the timeout mechanism of the PROFINET IO protocol. When a con-
nection loss is noticed, fault activation is started. If communication timeout value is zero, the fault
is activated immediately, otherwise the fault activates after a specified time. If the connection is re-
opened before the specified time has elapsed, no fault is created.
See Chapter 5.5.
4.3

Ethernet common settings

Usually in PROFINET IO network the PLC will set IP settings of the drive automatically when it tries
to connect to it. User only needs to set Profinet IO "Name Of Station" value which will used to identify
the drive in PLC program.
4
Table 6. PROFINET monitoring values
Min
Max
0
data
FFFFFFFF
0
FFFFFFFF
0
65535
0
outs
99999
0
FFFFFFFF
0
FFFFFFFF
0
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Unit
Default
8
-
0
hex
0
h
hex
0
h
-
0
d
-
0
d
hex
0
h
hex
0
h
Fieldbus parameterization
ID
Description
The number of additional
process data fields
2441
selected for
communication.
The latest control word
(vendor-specific format)
2442
received from the drive
application. (Can be used
for debugging purposes.)
The latest status word
(vendor-specific format)
2443
received from the drive
application. (Can be used
for debugging purposes.)
The number of
connection timeouts that
2444
have occurred in the
PROFINET IO protocol.
The number of
2445
parameter accesses
received by the device.
STW1 sent by master.
Not updated when
2595
vendor specific control
word is used.
ZSW1 sent to master.
Not updated when
2596
vendor specific control
word is used.
®
Live. Other possibility is to set

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VACON 100 industrial and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vacon 100 flowVacon 100 x

Table of Contents