Transmitter operation
8.7
Reset totalizers
Display
ProLink II
ProLink III
Field Communicator Service Tools > Variables > Totalizer Control > Mass > Mass Total
Overview
When you reset a totalizer, the transmitter sets its value to 0. It does not matter whether
the totalizer is started or stopped. If the totalizer is started, it continues to track process
measurement.
Tip
When you reset a single totalizer, the values of other totalizers are not reset. Inventory values are not
reset.
8.7.1
Reset totalizers using the display
Prerequisites
The Totalizer Reset display function must be enabled.
The totalizer that you want to reset must be configured as a display variable. For example:
•
•
Procedure
•
130
See
Section
8.7.1.
ProLink > Totalizer Control > Reset Mass Total
ProLink > Totalizer Control > Reset Volume Total
ProLink > Totalizer Control > Reset Gas Volume Total
ProLink > Totalizer Control > Reset
Device Tools > Totalizer Control > Totalizer and Inventories > Reset Mass Total
Device Tools > Totalizer Control > Totalizer and Inventories > Reset Volume Total
Device Tools > Totalizer Control > Totalizer and Inventories > Reset Gas Total
Device Tools > Totalizer Control > Totalizer and Inventories > Reset All Totals
Service Tools > Variables > Totalizer Control > Gas Standard Volume > Volume Total
Service Tools > Variables > Totalizer Control > Gas Standard Volume > GSV Total
Service Tools > Variables > Totalizer Control > All Totalizers > Reset All Totals
If you want to reset the mass totalizer, Mass Total must be configured as a display
variable.
If you want to reset the volume totalizer, Volume Total must be configured as a display
variable.
To reset the mass totalizer:
1. Scroll until the mass totalizer value appears.
2. Select.
®
Micro Motion
Model 1700 Transmitters with Analog Outputs