Troubleshooting
10.6
Milliamp output problems
Table 10-6:
Milliamp output problems and recommended actions
Problem
Possible causes
No mA output
•
•
•
Loop test failed
•
•
•
•
•
mA output below 4
•
mA
•
•
•
•
•
Constant mA output
•
•
•
•
•
184
Wiring problem
Circuit failure
Channel not configured for desired output
Power supply problem
Wiring problem
Circuit failure
Channel not configured for desired output
Incorrect internal/external power configu-
ration
Open in wiring
Bad output circuit
Process condition below LRV
LRV and URV are not set correctly
Fault condition if fault action is set to inter-
nal zero or downscale
Bad mA receiving device
Incorrect process variable assigned to the
output
Fault condition exists
Non-zero HART address (mA output 1)
Output is configured for loop test mode
Zero calibration failure
Recommended actions
•
Check the power supply and power supply
wiring. See
•
Check the mA output wiring.
•
Check the Fault Action settings. See
Section
•
Measure DC voltage across output termi-
nals to verify that the output is active.
•
Contact Micro Motion.
•
Check the power supply and power supply
wiring. See
•
Check the mA output wiring.
•
Check the Fault Action settings. See
Section
•
Contact Micro Motion.
•
Check your process conditions against the
values reported by the flowmeter.
•
Verify that the receiving device, and the
wiring between the transmitter and the re-
ceiving device.
•
Check the settings of Upper Range Value and
Lower Range Value. See
•
Check the Fault Action settings. See
Section
•
Verify the output variable assignments.
•
View and resolve any existing alarm condi-
tions.
•
Check the HART address and Loop Current
Mode. See
•
Check to see if a loop test is in process (the
output is fixed).
•
Check HART burst mode configuration.
See
Section
•
If related to a zero calibration failure, cycle
power to the meter and retry the zeroing
procedure.
®
Micro Motion
Model 1700 Transmitters with Analog Outputs
Section
10.9.
10.19.
Section
10.9.
10.19.
Section
10.18.
10.19.
Section
10.15.
10.16.