Using ProLink II with the transmitter
Figure B-8:
Connection over network
A
A. PC
B. Signal converter
Ω , 1/2-watt resistors at both ends of the segment, if necessary
C. 120-
D. DCS or PLC
E. Transmitter, with wiring compartment and power supply compartment opened
Note
This figure shows a serial port connection. USB connections are also supported.
4.
5.
6.
7.
8.
246
Start ProLink II.
Choose Connection > Connect to Device.
Set the connection parameters to the values configured in the transmitter.
If your transmitter has not been configured, use the default values shown here.
Table B-2:
Default Modbus/RS-485 connection parameters
Parameter
Protocol
Baud
Parity
Stop Bits
Address
Tip
If you do not know the transmitter's RS-485 communication settings, you can connect
through the service port, which always uses default settings, or use another communications
tool to view or change the settings.
Set the COM Port value to the PC COM port that you are using for this connection.
Click Connect.
D
C
B
Default value
Modbus RTU
9600
Odd
1
1
®
Micro Motion
Model 1700 Transmitters with Analog Outputs