Service Menus; Save/Restore Menu; Operating Hours - Daikin MicroTech III DPS Installation And Maintenance Manual

Iii unit controller for rebel refrigeration only controls
Table of Contents

Advertisement

Save/Restore Menu

The Save/Restore menu can be used to save or restore the
user configured parameters as well as reset the controller back
to the factory default parameters .
Table 19: Save/Restore Menu
Item Display
Default Setting
Name
Save Params=
No
Rstr Params=
No
Rstr Factory=
No
SaveToCard=
No
LoadFromCard=
No
CreateTrace=
No
TraceToSD=
No
Save Params is an adjustable item used to save the current
parameters and configuration.
Rstr Params is an adjustable item used to restore the current
parameters and configuration.
Rstr Factory is an adjustable item used to restore the factory
parameters and configuration.
SaveToCard is an adjustable item used to save the current
parameters and configuration to an SD card.
LoadFromCard is an adjustable item used to restore the
current parameters and configuration from an SD card.
NOTE: The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed .
OM 1263 • MICROTECH UNIT CONTROLLER
Range
Password Level
No
2
Yes
No
2
Yes
No
2
Yes
No
2
Yes
No
2
Yes
No
2
Yes
No
2
Yes

Operating Hours

The Operating Hours menu gives a summary of the hours of
operation for each of the supply fans, return/exhaust fans,
compressors, heating and economizer operation.
Table 20: Operating Hours Menu
Item Display
Default Setting
Name
Supply Fan=
Ret/Exh Fan=
Cmp Cooling=
INV Comp=
Comp 3=
Cmp Heating=
Supply Fan is a status item which gives the number of hours
the supply fan has operated .
Return/Exhaust Fan is a status item which gives the number
of hours the return/exhaust fans have operated .
Cmp Cooling is a status item which indicates the number of
hours compressor cooling has operated .
INV Comp is a status item which indicates the number of hours
the inverter compressor has operated .
Comp 3 is a status item which indicates the number of hours
the fixed speed compressor has operated.
Cmp Heating is a status item which indicates the number of
hours compressor heating has operated .
32

Service Menus

Service Menus
Range
Password Level
0 – 50000H
4
0 – 50000H
4
0 – 50000H
4
0 – 50000H
4
0 – 50000H
4
0 – 50000H
4
www .DaikinApplied .com

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroTech III DPS and is the answer not in the manual?

Table of Contents

Save PDF