Unit Configuration Setup Menu
After the main control board application software is loaded
into the MCB, it must be "configured" for the specific
control application . This consists of setting the value of 25
configuration variables within the MCB. These variables define
things such as the type of cooling, number of compressors and
cooling stages and the type of heat . If all of these items are not
set appropriately for the specific unit, the unit will not function
properly. The correct settings for these parameters are defined
for a given unit by the unit "Software Configuration Code."
The "Software Configuration Code" consists of a 29-character
string of numbers and letters . The code can be found on the
Unit Software Identification Label located on the back side of
the control panel door .
Table 29: Unit Configuration Menu
Configuration Code Position
1
2
3
4
5
6
7
8
9
10
11
12,13,14
15
OM 1263 • MICROTECH UNIT CONTROLLER
Description
Unit Type
Control Type
Cooling Type
Compressorized Cooling Configuration
Generic Condenser Stages
Low Ambient
Condenser Control
Damper Type
OA Flow Station
Heating Type
Max Heating Stages
Max Heat Rise
Supply Fan Type
Table 29
lists the configuration code variables including the
position within the code, description of the parameter, and the
applicable settings for each . The default values are shown
in bold font. The unit is configured at the factory however
may also be configured in the field by accessing the Unit
Configuration Menu. Once changes have been made to the
Unit Configuration Menu, the Apply Changes flag must be
changed from no to yes in order for the controller to recognize
the changes. Setting the Apply Changes flag to yes will
automatically rest the controller .
Values (Default in Bold)
3=Rebel Cool Only
4=Rebel Heat Pump
0=Zone Control
1=DAT Control
2=1ZoneVAV
3=RefOnly
0=None
4=Inverter Compressorized Clg
0=None
1=Generic Condenser
L=1INV/1Circ
M=1INV/1STD/1Circ
1-8 Stages (Default 8)
0=None
1=Yes
7=EBM
8=INV
9=INVMC
0=None
1=Single Position 30%
2=Single Position 100%
3=Economizer Airside
5=100%OA_DOAS
6=AirEcon_DOAS
7=3-% DOAS
0=None
5=Generic Flow Station
6=Generic Flow Station w/CO
2
0=None
1=F&BP Control
2=Staged
5=Steam or Hot Water
6=SCR Electric
7=MOSLoGas
8=MOSHiGas
1-8 Stages (Default =1)
Three Digits (Default = 100)
6=EBMVAV
7=EBMCAV
36
Unit Configuration Setup
Unit Configuration Setup
"ROC
Applicability"
●
NA
NA
NA
●
NA
●
●
NA
●
●
NA
NA
●
●
●
●
●
NA
NA
NA
●
●
NA
●
NA
●
●
●
●
●
●
●
●
www .DaikinApplied .com