ERROR CODE: L9 – Inverter Compressor Starting Failure
L9
Remote
Controller
Display
Method of
Detect the failure based on the signal waveform of the compressor .
Malfunction
Detection
Malfunction
Starting the compressor does not complete .
Decision
Condition
● Defective compressor
● Wiring connection error to the compressor
Supposed
Causes
● Large pressure difference before starting the compressor
● Defective inverter PC board
OM 1263 • MICROTECH UNIT CONTROLLER