Error Code: L8 - Momentary Overcurrent Of; Inverter Compressor - Daikin MicroTech III DPS Installation And Maintenance Manual

Iii unit controller for rebel refrigeration only controls
Table of Contents

Advertisement

ERROR CODE: L8 – Momentary Overcurrent of Inverter Compressor
L8
Remote
Controller
Display
Method of
Malfunction is detected from current flowing in the power transistor.
Malfunction
Detection
When overload in the compressor is detected . (Inverter secondary current 16 . 1 A)
For 460V units
(1) 19 .0A and over continues for 5 seconds .
Malfunction
(2) 16 . 1 A and over continues for 260 seconds .
Decision
Condition
For 230V units
(1) A current of 33 .5A or more continues for a period of consecutive 5 sec .
(2) A current of 27 .6A or more continues for a period of consecutive 260 sec .
● Compressor overload
● Compressor coil disconnected
Supposed
Causes
● Defect of inverter PC board
● Faulty compressor
OM 1263 • MICROTECH UNIT CONTROLLER
88
Troubleshooting
www .DaikinApplied .com

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroTech III DPS and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF