3 I N S TA L L AT I O N

3 .2 Site planning and positioning

3.2.1-1:
Ear bracket
3.2.1-2:
Rack rails
WARNING
3.2.1-3:

Rack-mount installation

3 .2 .1 Planning before the installation

To ensure a long service life, install the unit
in a position where any danger to the UPS
is minimized:
• Install the UPS indoors.
• Leave enough space on each side of the cabinet
to allow cooling airflow and ensure that the
circulation of air to the ventilation slits is not
obstructed.
• Avoid excessively high temperatures and
excessive moisture.
• Make sure that the surface is solid and flat.

3 .2 .2 Positioning

PowerValue 11 RT G2 can be mounted in a rack
or installed in a standalone configuration.
WARNING
WARNING
3 .2 .3
WARNING
3 .2 .3 .1 UPS
Note that you need a rack-mounting kit
(purchased separately) for this operation. This
procedure is suitable for 19-inch rack cabinet
installation with a minimum depth of 800 mm.
Identify the final position and keep 2U spacing
for this installation.
• MAKE SURE THE MAINS SUPPLY AND THE TOTAL LOAD DEMAND ARE WITHIN UPS SPECIFICATIONS
• THE UPS MUST BE POWERED FROM A SINGLE-PHASE GROUNDED WALL OUTLET, PROTECTED BY
OVERCURRENT DEVICES ACCORDING TO LOCAL WIRING RULES (NOT APPLICABLE FOR POWERVALUE 11
RT G2 3KVA S)
• THE PLUG ON THE POWER SUPPLY CORD IS INTENDED TO SERVE AS THE DISCONNECT DEVICE, THE
MAINS SOCKET OUTLET THAT SUPPLIES THE UPS SHALL BE INSTALLED NEAR THE UPS AND SHALL BE
EASILY ACCESSIBLE (NOT APPLICABLE FOR POWERVALUE 11 RT G2 3KVA S)
• AFTER REMOVING COVERS OVER BATTERY TERMINAL, STORE THEM SAFELY FOR FUTURE NEED. REMOVE
SUCH COVERS ONLY IF IT IS INTENDED TO ATTACH A CONNECTOR TO A TERMINAL.
WATER CONDENSATION MAY OCCUR IF
THE UPS IS UNPACKED IN A VERY LOW
TEMPERATURE. TO AVOID HAZARDS AND
RISK OF ELECTRIC SHOCK, WAIT UNTIL
THE UPS IS FULLY DRY BOTH INSIDE AND
OUTSIDE BEFORE INSTALLING/USING
THE UPS.
HANDLE THE UPS CAREFULLY TO AVOID
INJURY FROM FALLING OBJECTS
REFER TO THE TECHNICAL DATA SHEET
FOR UPS WEIGHTS.
Rack-mount installation
TO AVOID INJURY FROM FALLING OBJECTS
MAKE SURE THAT THE RACK CABINET CAN
ACCEPT THE UPS WEIGHT BEFORE
INSTALLING IT, INCLUDING PROVISIONS
FOR FIXING THE UPS BY SCREW.
IT IS RECOMMENDED TO INSTALL THE
BATTERY STARTING FROM THE BOTTOM
OF THE RACK
3.2.1-1
3.2.1-2
3.2.1-3
9