Electrical Installation; Ups Input/Output Connection; Commissioning; Recommended Cable Sections And Fuse Ratings - ABB PowerValue 11 RT G2 IN User Manual

Hide thumbs Also See for PowerValue 11 RT G2 IN:
Table of Contents

Advertisement

U S E R M A N U A L
3.3.2-4
PowerValue 11 RT G2 - 3kVA B rear view
3.3.2-5
External battery - module rear view

3.4 Electrical installation

3.4.1 UPS input/output connection

If the UPS input is connected with power cord,
simply plug the UPS input power plug to wall
socket. For the output connection with socket,
plug the UPS into a proper socket (grounded and
shockproof) and pay attention to the capacity of
the socket. Avoid using extension cords. For
PowerValue 11 RT G2 3kVA mode, please refer to
3.4.4 for input/output wiring.

3.4.2 Commissioning

The commissioning of the UPS includes the
connection of the UPS and batteries, the
verification of the electrical installation and
operating environment of the UPS, the controlled
start-up and testing of the UPS, and customer
training.
WARNING!
Do not operate in case of presence
of water or moisture.
DANGER!
When opening or removing the UPS
covers you are exposed to
dangerous voltages.
3.4.3 Recommended cable sections and fuse
ratings
When selecting the cable cross-sections and the
protective devices, follow the recommendations
in the technical specifications document or follow
local standards.
DANGER!
To reduce the risk of fire, connect only
to a circuit provided with 15 A maximum
branch circuit. Overcurrent protection
in accordance with the National
Electrical Code, ansi/nfpa 70 and the
Canadian Electrical Code, PART I, C22.1.
3.4.3-1
Circuit breaker
Table 4: Recommended cable cross sections
Model
PowerValue 11 RT G2 3kVA
Input L, N, G
1.5 mm^2
(min. conductor
(14 AWG)
cross-section)
Input fuse
15 A
Output L,N,
1.5 mm^2
(min. conductor
(14 AWG)
cross-section)

3.4.4 PowerValue 11 RT G2 3kVA installation

15