2.1.3 BLOCK DIAGRAM CONCEPTPOWER DPA
2.1.3.1
Single Feed input (Standard Version)
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Fuse
A
Cable A
F1 F2
Rectifier
Cable E
Fuse E
Inverter
Static Switch
IA2-1
Frame
Input 3x400V
Load
Frame
kVA
Fuse A
cosphi
type
(Agl/CB)
0.8
MX Frames (Frames shall be cabled to there full rating capability)
CLASSIC
50
3x100A
DPA 50
TRIPLE
150
3x250A
DPA-150
UPGRADE
250
3x400A
DPA-250
MAINS 3x400/230V
F1 F2
Rectifier
Inverter
Static Switch
IA2-2..4
Maintenance Bypass IA1
Cable D
Load 3x400/230 V
Max. Input
Current
2
Cable A (mm
)
with
battery
(IEC 60950-1)
charging
(A)
5x25
67
5x120 or 5x(2x50)
202
5x(2x95)
337
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
STANDARD VERSION (SINGLE FEED INPUT)
F1 F2
Rectifier
Inverter
Static Switch
IA2-5
Output 3x400V cosphi 0.8
2
Cable D (mm
)
I nom
(A)
(IEC 60950-1)
5x25
72 A
5x120 or 5x(2x50)
218 A
5x(2x95)
362 A
Section-2
Battery
Cable E (mm
for CBAT DPA 120 or 200
Fuse E
ONLY
+ / N / -
+ / N / -
(Agl/CB)
Com. Battery
Sep. Battery
3x100A*1
3x25
3x300A*1
3x150
3x (3x25)
3x500A*1
3x(2x150)
5x (3x25)
*1 only valid for common battery use
Page 3/16 ABB
2
)
3x25