Monitoring Of Lower Endstop 'F.\\Zero - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
9.4 Description of parameters
9.4.3.6

Monitoring of lower endstop 'F.\\ZERO'

F. ZERO - Monitoring of lower endstop
Note
Fault detection
Monitoring of lower endstop not only responds to faults in the valve. If the limit thresholds of
the lower endstop are exceeded due to misalignment of the position feedback, the
misalignment also triggers a diagnostics message.
Requirement:
Possible settings:
Purpose:
Factory setting:
F1.LEVL1 - threshold 1
Adjustment range:
Purpose:
Factory setting:
180
The '52.XDIAG' Activating for extended diagnostics (Page 166) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
The '39.YCLS' Tight closing/fast closing with manipulated variable
(Page 157) parameter is set to one of the following values: 'do',
'uP do', 'Fd', 'Fu Fd', 'uP Fd', 'Fu do'.
● OFF
● On
Use this parameter to activate continuous monitoring of the lower
endstop. Monitoring is always carried out if the '39.YCLS' Tight clos‐
ing/fast closing with manipulated variable (Page 157) parameter is
set to one of the following values: 'do', 'uP do', 'Fd', 'Fu Fd', 'uP Fd',
'Fu do'
It checks whether the lower endstop has changed compared to its
value during initialization. Monitoring is performed in three steps.
Set the following sub-parameters appropriately. To activate moni‐
toring, set the parameter to 'On'. Sub-parameters are displayed.
The current value is displayed in Diagnostic value '18.ZERO - Lower
endstop' (Page 206). The positioner triggers a message if the cur‐
rent value undershoots one of the three thresholds.
OFF
0.1 ... 10.0
Use this sub-parameter to set threshold 1 for the lower endstop in
percent. Set the threshold in a range from '0.1' to '10.0'.
The positioner triggers a threshold 1 message if the difference be‐
tween the lower endstop and the initialization value undershoots
threshold 1. This message is only output if threshold 2 or 3 is not
unsershot at the same time. The process to activate and display this
message is described in the 'XDIAG' parameter.
1.0
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC