Yway' Range Of Stroke - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Factory setting:
See also
Sequence of automatic initialization (Page 108)
9.4.1.3

'3.YWAY' Range of stroke

Requirement:
Possible settings:
Purpose:
Factory setting:
See also
'1.YFCT' type of actuator (Page 147)
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
'2.YAGL' can only be adjusted if '1.YFCT' is set to 'WAY'/'-WAY' or
'FWAY'/'-FWAY'.
With all other settings of '1.YFCT', an angle of 90° is automatically
set for '2.YAGL'.
33°
● Positioner is mounted.
● Carrier pin is mounted on the lever in accordance with the
actuator's range of stroke as described in section Mounting the
linear actuator (Page 36), Mounting the linear actuator
(Page 36).
● OFF
● 5.0 | 10.0 | 15.0 | 20.0 | 25.0 |30.0 | 35.0 | 40.0 |
50.0 | 60.0 | 70.0 | 90.0 | 110.0 | 130.0
Use this parameter to display the determined stroke value in mm
when initialization of a linear actuator has been completed.
If you select the 'OFF' setting, the real stroke is not displayed after
initialization.
From the possible settings shown above, select the value which
corresponds to the range of stroke of your actuator in mm.
If the range of stroke of the actuator does not correspond to a pos‐
sible setting, use the next higher value. Use the value specified on
the nameplate of the actuator for this purpose.
'3.YWAY' is only displayed if '1.YFCT' is set to 'WAY'/'-WAY' or
'ncSLL'/'-ncLL'.
OFF