Installing/mounting
4.6 Installing option modules
Procedure for installing the internal NCS module
1. You have performed the steps described in the section General information on installing
option modules (Page 51).
The legend numbers refer to the indicated section. The legend letters refer to the figures
in this section.
2. Unplug the ribbon cable connector
electronics
3. Remove the basic electronics
that fasten the basic electronics to the pneumatic block
4. Insert the connector of the ribbon cable (A) into the slot as shown below.
Note: There is no space for the ribbon cable (A) in earlier versions of the positioner. Here
you fasten the ribbon cable to the container using a cable tie.
5. Screw the special screw (E) into the shaft of the positioner. Tighten the special screw (E)
with a torque of 2 Nm.
6. Press the adjustment wheel of the magnet clamp (F) firmly onto the special screw (E) of
the friction clutch until you clearly hear it click into place.