Initializing the linear actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, keep the
seconds. The display shows the following:
2. Call the "2.YAGL" parameter. To do this, press
depending on the setting:
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the
transmission ratio selector. If required, change the setting of the transmission ratio selector
to 33° or 90°.
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of parameter
3 is optional. The display shows the determined total stroke only at the end of the
initialization phase.
– Press the
– Call the "3.YWAY" parameter. To do this, press
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
button if you do not require any information about the total stroke in mm.
You are then directed to parameter 4.
Note
Set the "3.YWAY" parameter
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons
7.5 Commissioning linear actuators
button pressed for at least 5
. The following is shown on the display
. The display shows the following:
and
to the read value.
Commissioning
. The settings
117