Purpose:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Start the function by pressing the
The display shows 'WAit' during these 5 seconds. Set the desired
function after 5 seconds.
Std
Setting for a standard pneumatic block
FIP
If you order a positioner for Fail in Place applications, it is
then equipped with a special pneumatic block. The
"PNEUM" parameter is preset to "FIP". The parameter
must be set to "FIP" again when the basic electronics are
replaced.
booSt
Use this function if you operate the positioner with a boos‐
ter. This function then shows the actuator overshoot. You
can find a description of how to operate the booster under
Booster (Page 289).
Parameter assignment
9.4 Description of parameters
button for at least 5 seconds.