Controller - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Technical data

12.4 Controller

Construction
Screw-in torque for NPT adapter made of metal/stainless
steel in polycarbonate enclosure
Screw-in torque for NPT adapter made of metal/stainless
steel in aluminum/stainless steel enclosure
Screw-in torque for NPT gland in the NPT adapter
NOTE: To avoid damage to the device, the NPT adapter
must be held in place while the NPT gland is screwed
into the NPT adapter.
Tightening torque for union nut made of plastic
Tightening torque for union nut made of metal/stainless
steel
Manometer
● Degree of protection
Manometer made of plastic
Manometer, steel
Manometer made of stainless steel 316
● Vibration resistance
Connections, electrical
Screw terminals
● Cable gland
Connections, pneumatic
12.4
Controller
Controller
Control unit
● Five-point controller
● Dead zone
dEbA = auto
dEbA = 0.1 ... 10 %
Analog-to-digital converter
● Scanning time
● Resolution
● Transmission error
● Temperature influence
234
8 Nm (5.9 ft lb)
15 Nm (11.1 ft lb)
68 Nm (50 ft lb)
2.5 Nm (1.8 ft lb)
4 Nm (3 ft lb)
IP31
IP44
IP54
In accordance with DIN EN 837-1
2.5 mm
AWG30-14
2
Without Ex protection as well as with Ex i: M20x1.5 or ½-14
NPT
With explosion protection Ex d: Ex d certified M20x1.5,
½-14 NPT or M25x1.5
Female thread G¼ or ¼-18 NPT
Adaptive
Adaptive
Can be set as fixed value
10 ms
≤ 0,05 %
≤ 0,2 %
≤ 0.1 %/10 K (≤ 0.1 %/18 °F)