Protection level
● ia: Protection level. Electric equipment operating fault-free, and with existence of two
countable errors.
● ib: Protection level. Electric equipment operating fault-free, and with existence of one
countable error.
● ic: Protection level. Electrical equipment is not able to cause an ignition when operating
fault-free.
Protocols
Protocols contain information about data formats, time sequences and error handling when
exchanging data between computers.
A protocol is a convention about establishing, monitoring and terminating a connection.
Different protocols are required for a data connection. Protocols can be assigned to every layer
of the reference model. Transport protocols are used for the lower four layers of the reference
model and higher protocols are used for control, data provision and application.
Safety function
Defined function executed by a safety-instrumented system with the objective of attaining or
maintaining a safe status of the system by taking a defined hazardous incident into account.
Example: limit pressure monitoring
Safety-instrumented system
A safety-instrumented system (SIS) executes safety functions that are required to attain or
maintain the safe status in a system. It consists of sensors, logic unit/control system and final
controlling elements.
Example: a safety-instrumented system consists of a pressure transmitter, a limit signal
indicator and a servo valve.
Sensor
Converter that converts mechanical or other non-electric variables into electric signals.
SIL
The international standard IEC 61508 defines four discrete safety integrity levels (SIL) from
SIL 1 to SIL 4. Every level indicates a probability range for the failure of the safety function.
The higher the SIL of the safety-instrumented system, the higher the probability that the
required safety function works. The achievable SIL is determined by the following safety-
instrumented characteristics:
● Average probability of dangerous failures of a safety function on demand (PFDAVG)
● Hardware fault tolerance (HFT)
● Safe failure fraction (SFF)
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Glossary
313