9.4

Description of parameters

9.4.1

Initialization parameters 1 to 5

9.4.1.1

'1.YFCT' type of actuator

Requirement:
Possible settings:
Purpose:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Type of actuator as well as mounting type and direction of action
are known.
Actuator with normal direction of
action
● turn
● WAY
● FWAY
● LWAY
● ncSt
● ncSL
● ncSLL
Use this parameter to adjust the positioner to the respective actua‐
tor.
● turn/-turn: Use this setting for a part-turn actuator with a directly
mounted positioner.
● WAY/-WAY: Use this setting for a linear actuator with a carrier
pin mounted on the lever.
● FWAY/-FWAY: Use this setting for a linear actuator with a carrier
pin mounted on the actuator spindle.
● LWAY/-LWAY: Use this setting for an external linear
potentiometer on a linear actuator (e.g. with cylinder drives).
● ncSt/-ncSt: Use this setting for a part-turn actuator for:
– An NCS sensor 6DR4004-. N.10 and -.N.40
– Internal NCS module
● ncSL/-ncSL: Use this setting for an NCS sensor 6DR4004-.N.20
on a linear actuator for strokes < 14 mm (0.55 inch).
● ncSLL/-ncLL: Use this setting for a linear actuator for:
– An NCS sensor 6DR4004-.N.30 for strokes > 14 mm
(0.55 inch).
– An internal NCS module. No limitations apply to the internal
NCS module.
In the case of actuators with inverted direction of action, use the
settings with the minus sign, e.g. -turn.
Parameter assignment
9.4 Description of parameters
Actuator with inverted direction of
action
● -turn
● -WAY
● -FWAY
● -LWAY
● -ncSt
● -ncSL
● -ncLL