B.2.2

Mounting the NCS

Function
The positioner facilitates the separate installation of the position detection system. The stroke
or rotary angle is measured directly at the actuator by means of a non contacting sensor. It is
therefore possible to install the controller unit at some distance away, e.g. on a mounting pipe
or similar. The positioner is connected to the position detection system by means of an
electrical cable.
Such a separate installation is useful whenever the ambient conditions at the valve exceed
the specified positioner values.
The NCS consists of a molded sensor for fixed installation and a magnet. The magnet is
mounted to the spindle on linear actuators, or to the stub shaft on part-turn actuators. The
sensor housing is mounted onto the console on part-turn actuators and to the bracket on linear
actuators. The bracket can be a NAMUR type, or any other mounting bracket.
Auxiliary power is supplied to the NCS via the EMC filter module C73451-A430-D23 and EMC-
compatibility is ensured at the same time.
EMC filter module ordering options:
● Installed in the positioner; see Catalog FI 01
● For retrofitting in the positioner; Order No. C73451-A430-D23. For information on retrofitting
the EMC filter module, refer to the positioner operating instructions, chapter "Installation/
Mounting".
Figure B-3
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
External position detection with NCS or external position detection system
Pneumatic line
Pneumatic line for double-action actuators
Position detection system (10 kΩ potentiometer, or NCS)
Electrical cable
Retrofittable EMC filter module (in the positioner)
Positioner
Separate installation of the NCS and positioner
B.2 Non-Contacting Sensor