Siemens SIPART PS2 Operating Instructions Manual page 279

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Preparing the positioner
1. You have performed the steps described in the section "General information on installing
option modules (Page 51)".
2. Unplug the ribbon cable connector
3. Remove the basic electronics
that fix the basic electronics to the pneumatic block.
4. Loosen screw
5. Insert the connector of the ribbon cable (A) into the slot as shown below.
Note: There is no space for the ribbon cable (A) in earlier versions of the positioner. Here
you fasten the ribbon cable with the supplied cable tie at the container.
6. Secure the EMC filter module using the screw
7. Fit the basic electronics
8. Insert the ribbon cable connector
electronics.
9. In non-hazardous environment:
– Stick the supplied nameplate over the nameplate on the external position detection
– Remove the Ex label mounted on the side opposite the nameplate
– Replace the blue cable gland
Refer to section "Scope of delivery of external position detection system (Page 281)", items
"Nameplate for device version without explosion protection" and "Gray cable gland".
Procedure for connecting an external position detection system
1. Connect the three terminals of the external position detection system
terminals of the EMC filter module
2. Tighten the cable glands
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
External position detection with NCS or external position detection system
.
in the connection area of the positioner.
system
.
to the fitted potentiometer from the basic electronics
from the positioner. To this end, remove the two screws
loosened in the third step.
back into the positioner.
of the EMC filter module onto the positioner basic
by the supplied gray cable gland.
using a cable as shown in the wiring diagram.
and
.
B.3 External position detection system
to the three