7. Position the ribbon cable of the internal NCS module (D) upwards, as shown in the figure,
before you slide the internal NCS module into the rack.
8. Slide the internal NCS module (B) under the basic electronics into the rack until you hear
it click into place.
9. An insulating cover is required over the internal NCS module. This insulating cover is
supplied with the internal NCS module. Place the insulating cover (C) on one side under
the basic electronics seat of the rack.
10.Now position the insulating cover by pressing one end against the seat of the rack and
slowly lowering the other end.
11.Firmly press the other end until the insulating cover is underneath the contact surface of
the basic electronics. The recesses of the insulating cover must fit in the corresponding
webs of the rack.
12.Install the basic electronics back into the positioner.
13.Insert the ribbon cable connector of the internal NCS (D) module onto the positioner basic
electronics.
Note for installed position feedback module: Reestablish all electrical connections between
the basic electronics and the position feedback module.
14.Using both the screws, fasten the module cover provided. Do not use the standard module
cover of the positioner. The provided module cover has a larger recess to accommodate
the adjustment wheel of the magnet clamp (F).
15.Make sure that the ribbon cable is not trapped.
16.Select the labels that already exist on the standard version of the module cover from the
label set provided. Affix the selected labels on the installed module cover as per the
standard version.
17.Proceed with the corresponding steps in the section General information on installing option
modules (Page 51).
Result
The internal NCS module is installed and connected to the basic electronics of the positioner.
Now configure the internal NCS module with the parameters '1.YFCT', Overview of initialization
parameters 1 to 5 (Page 139) and '1.YFCT' type of actuator (Page 147).
4.6.7

EMC filter module

Function
You will require the EMC filter module if you use an external position sensor on the positioner,
e.g. a potentiometer or a non-contacting sensor. The EMC filter module forms the interface
between external position sensors and the basic electronics of the positioner. This module
protects the positioner from electromagnetic effects.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Installing/mounting
4.6 Installing option modules