Parameter assignment
8.3 Description of parameters
8.3.3.6

Monitoring the lower endstop ''F.\\ZERO'

F. ZERO - Monitoring of lower endstop
Note
Fault detection
Monitoring of lower endstop not only responds to faults in the valve. If the limit thresholds of the
lower endstop are exceeded due to misalignment of the position feedback, the misalignment
also triggers a diagnostics message.
Requirement:
Possible settings:
Purpose:
Factory setting:
F1.LEVL1 - threshold 1
Adjustment range:
Purpose:
Factory setting:
176
The '50.XDIAG' Activation of extended diagnostics (Page 160) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
The ' 36.YCLS' Tight closing/fast closing with manipulated variable
(Page 150) parameter is set to one of the following values: 'do',
'uP do', 'Fd', 'Fu Fd', 'uP Fd', 'Fu do'.
● OFF
● On
Use this parameter to activate continuous monitoring of the lower
endstop. Monitoring is always carried out if the '37.YCDO' Value for
tight closing/fast closing Down (Page 151) parameter is set to one
of the following values: 'do', 'uP do', 'Fd', 'Fu Fd', 'uP Fd', 'Fu do'
It checks whether the lower endstop has changed compared to its
value during initialization. Monitoring is performed in three steps.
Set the following sub-parameters appropriately. To activate moni‐
toring, set the parameter to 'On'. Sub-parameters are displayed.
The current value is displayed in Diagnostic value '18.ZERO - Low‐
er endstop' (Page 264). The positioner triggers a message if the
current value undershoots one of the three thresholds.
OFF
0.1 ... 10.0
Use this sub-parameter to set threshold 1 for the lower endstop in
percent. Set the threshold in a range from '0.1' to '10.0'.
The positioner triggers a threshold 1 message if the difference be‐
tween the lower endstop and the initialization value undershoots
threshold 1. This message is only output if threshold 2 or 3 is not
unsershot at the same time. The process to activate and display this
message is described in the 'XDIAG' parameter.
1.0
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC