Installing/mounting
4.6 Installing option modules
Device features
①
②
③
Figure 4-14
The mechanical limit switch module consists of:
● One binary output to display a collective fault message. Compare with the device features
of the alarm module.
● Two switches to report two mechanically adjustable limits. Both these switches are
electrically independent from the remaining electronic unit.
Requirements
You are familiar with the procedure described in section Installing optional modules in the
standard and intrinsically safe version (Page 51).
Procedure for installing the mechanical limit switch module
1. Disconnect all electrical connections of the basic electronics.
2. Loosen the two fixing screws of the basic electronics.
3. Remove the basic electronics.
4. Insert the mechanical limit switch module from the top up to the upper printed circuit board
guide of the module rack.
5. Slide the mechanical limit switch module in the printed circuit board of the module rack
approximately 3 mm towards right.
64
Actuating disk bearings
Special screw
Pin
Mechanical limit switch module
④
Upper actuating disk for limit L1, terminals
41/42
⑤
Lower actuating disk for limit L2, terminals
51/52
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC