Advertisement

Parameter assignment
8.3 Description of parameters
Purpose:
Factory setting:
See also
Sequence of automatic initialization (Page 111)
8.3.1.3

'3.YWAY' Range of stroke

Condition:
Possible settings:
Purpose:
Factory setting:
144
Use this parameter for a linear actuator. For a linear actuator, set an
angle of 33° or 90° depending on the range of stroke. The current
setting of the actuator is then measured more accurately. The fol‐
lowing is applicable:
● 33°: Strokes ≤ 20 mm
● 90°: Strokes 25 mm to 35 mm
● 90°: Strokes > 40 mm to 130 mm
Use the mounting kit:
● 6DR4004-8V for strokes up to 35 mm
● 6DR4004-8L for strokes greater than 35 mm up to 130 mm
'2.YAGL' can only be adjusted if '1.YFCT' is set to 'WAY'/'-WAY' or
'FWAY'/'-FWAY'.
With all other settings of '1.YFCT', an angle of 90° is automatically
set for '2.YAGL'.
33°
● Positioner is mounted.
● Carrier pin is mounted on the lever in accordance with the
actuator's range of stroke as described in section Mounting to
linear actuator (Page 42).
● OFF
● 5.0 | 10.0 | 15.0 | 20.0 | 25.0 |30.0 | 35.0 | 40.0 |
50.0 | 60.0 | 70.0 | 90.0 | 110.0 | 130.0
Use this parameter to display the determined stroke value in mm
when initialization of a linear actuator has been completed.
If you select the 'OFF' setting, the real stroke is not displayed after
initialization.
From the possible settings shown above, select the value which
corresponds to the range of stroke of your actuator in mm.
If the range of stroke of the actuator does not correspond to a pos‐
sible setting, use the next higher value. Use the value specified on
the nameplate of the actuator for this purpose.
'3.YWAY' is only displayed if '1.YFCT' is set to 'WAY'/'-WAY' or
'ncSLL'/'-ncLL'.
OFF
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC