Connection Settings

This section describes the settings for client/server communication during TCP/IP communication using Ethernet port 1 or the
HMI-Ethernet port of the FC6A Series MicroSmart.
Applications
The FC6A Series MicroSmart is capable of maintenance communication, user communication, and Modbus TCP communication
using a maximum of eight connections over Ethernet port 1.
Those communications can be configured in the Function Area Settings dialog box.
Also, the HMI-Ethernet port can be used to expand a maximum of eight connections when using an HMI module.
However, the only communication function that is supported by the HMI-Ethernet port is maintenance communication.
Description of functions
Each connection can be selected as maintenance communication server, user communication server, user communication client,
Modbus TCP server, Modbus TCP client, or unused, and a maximum of eight connections can be configured.
To limit the access to the FC6A Series MicroSmart, IP address flittering can be used. By specifying the IP address that can access
the FC6A Series MicroSmart, anonymous access can be prevented.
Communication Mode
Maintenance
communication server
(Default)
User communication
server
User communication client
Modbus TCP server
Modbus TCP client
Unused
Connection Status and Connected IP Address
The connection status of connections with remote hosts can be confirmed with special internal relays M8212 to M8221. When a
connection with a remote host is established, the corresponding special internal relay is turned on. When the connection is
disconnected, the corresponding special internal relay is turned off. The IP addresses of the remote hosts can be confirmed with
special data registers D8350 to D8381.
Note: R/W is the abbreviation for read/write. When R/W, it can be read and written. When R, it can only be read. When W, it can only be written.
Special Internal Relays
Device Address
M8212
M8213
M8214
M8215
M8216
M8217
M8220
M8221
M8222
M8223
M8224
M8225
M8226
M8227
M8230
M8231
This mode allows monitoring and changing devices and user program uploading and downloading
from WindLDR.
This mode enables communication with client devices according to the ETXD (Ethernet user
communication transmit) instruction and the ERXD (Ethernet user communication receive) instruction.
This mode enables communication with server devices according to the ETXD (Ethernet user
communication transmit) instruction and the ERXD (Ethernet user communication receive) instruction.
When the FC6A Series MicroSmart is configured as a Modbus TCP server, FC6A Series MicroSmart data
monitoring and modifications can be executed from Modbus TCP client-compatible devices.
Modbus TCP server-compatible device data monitoring and modifications can be executed from
Modbus TCP clients.
The connection is not used.
Description
Connection 1 Status
Connection 2 Status
Connection 3 Status
Connection 4 Status
Connection 5 Status
Connection 6 Status
Connection 7 Status
Connection 8 Status
Connection 1 disconnected flag
Connection 2 disconnected flag
Connection 3 disconnected flag
Connection 4 disconnected flag
Connection 5 disconnected flag
Connection 6 disconnected flag
Connection 7 disconnected flag
Connection 8 disconnected flag
FC6A S
M
S
A
ERIES
ICRO
MART
LL
Overview
While a connection is established with a remote host, the
special internal relay will be on. When no connection is
established, it will be off.
When turned on, the connection to the server is forcibly
disconnected to stop communication. When turned off,
the connection to the server is established and
communication is restarted.
This flag is only valid in user communication client and
Modbus TCP client.
-
-O
T
C
IN
NE
YPE
OMMUNICATION
3: C
OMMUNICATION
Details
M
FC9Y-B1730
ANUAL
S
ETTINGS
Reference
4-6
5-40
5-37
6-24
6-19
Read/Write
R
R/W
3-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents