Function Code 06 (Preset Single Register)
Function code 06 changes word device data of D (data register).
Communication Frame
Request from Modbus RTU Master
Slave No.
xxh
ACK Reply from Modbus RTU Slave
Slave No.
xxh
NAK Reply from Modbus RTU Slave
Slave No.
xxh
Communication Example
Write 8000 to data register D1708.
D1708 → (1708 – 0) + 400001 = 401709
Modbus address: 401709
Purpose
Extract lower 5 digits → 1709
1709 – 1 = 1708 = 6ACh
Communication frame address: 06ACh
Condition
Slave No. 8
Modbus RTU Mode
Request from Modbus RTU Master
ACK Reply from Modbus RTU Slave
NAK Reply from Modbus RTU Slave
Function Code
Address
06h
xxxxh
Function Code
Address
06h
xxxxh
Function Code
Error Code
86h
xxh
08 06 06AC 1F40 (CRC)