Click Communication Mode for port 1 and select Maintenance Protocol.
2.
The Maintenance Protocol (Port1) dialog box appears.
3.
Configure the parameters to match the communication settings of the computer or operator interface.
Baud Rate (bps):
Data Bits:
Parity:
Stop Bits:
Receive Timeout (ms):
Slave Number:
Click OK.
4.
Configuring the maintenance communication for the expansion communication port is now complete.
FC6A S
115200 bps (1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
7 (7 or 8)
Even (None, Even, Odd)
1 (1 or 2)
500 (10 to 2550)
0 (0 to 31)
Slave number can be specified by either a constant or a data register.
Type
Details
Constant
Set within the range of 0 to 31
Store the slave numbers 0 to 31 in the following special data registers
Port 1: D8100
Data register
Port 2: D8102
Port 3: D8103
M
S
A
-
ERIES
ICRO