IDEC FC6A-C16K1CE Communications Manual page 188

Fc6a series microsmart all-in-one type
Hide thumbs Also See for FC6A-C16K1CE:
Table of Contents

Advertisement

8: J1939 C
OMMUNICATION
(4) Message parameter settings
These settings configure the details of the transmitted message selected in the message list.
CAN ID
PGN:
Sets the PGN of the message to transmit. The range of the PGN that can be set is 0 to 61,184 (0000h to EF00h)
(PDU1 format). Set the low order 1 byte (PDU Specific) that indicates the destination address in PDU1 format to
00h.
Click ... and a PGN can be selected in the displayed PGN Manager. For details, see "PGN Manager" on page 8-29.
Priority:
Sets the priority for the message to transmit between 0 and 7.
Type
Sets the transmit method for the message. Select as "Event" or "Cycle".
Event:
Designated CA event transmission example
M8301
J1939 online status
Transmit trigger
Ladder program
END processing
Data storage destination DR
Transmit buffer
Cycle:
Designated CA cycle transmission example
M8301
J1939 online status
Cycle transmission
permitted flag
Ladder program
END processing
Data storage destination DR
Transmit buffer
Maximum data length
Sets the maximum data length of the PGN to transmit. The maximum value that can be set is 252 bytes.
Transmit cycle (ms)
Sets the transmit cycle in 10 ms increments when "Cycle transmission" is selected for Type. The range of the value that can be
set is 10 to 655,350.
8-20
When the transmit trigger is turned on, the transmit data stored in the data storage destination is
transmitted in END Processing.
ON
OFF
ON
OFF
ON
OFF
CAN
While the cycle transmission permitted flag is on and when the transmit cycle occurs, the transmit data
stored in the data storage destination is transmitted in END processing. The actual transmit cycle is
affected by the ladder program scan time.
ON
OFF
ON
OFF
ON
OFF
CAN
FC6A S
M
S
A
ERIES
ICRO
MART
Transmit cycle
Message A
Message A
Message A
-
-O
T
C
LL
IN
NE
YPE
OMMUNICATION
Message A
Message A
Message A
Transmit cycle
Message B
Message A
Message B
Message A
M
FC9Y-B1730
ANUAL
Transmit cycle
Message B

Hide quick links:

Advertisement

Table of Contents
loading