Function Code 03 (Read Holding Registers) and Function Code 04 (Read Input Registers)
Function code 03 reads word device data of D (data register), T (timer preset value), or C (counter preset value). 1 through 64
consecutive words can be read out.
Function code 04 reads word device data of T (timer current value) or C (counter current value). 1 through 64 consecutive words
can be read out.
Communication Frame
Request from Modbus RTU Master
Slave No.
xxh
ACK Reply from Modbus RTU Slave
Slave No.
xxh
NAK Reply from Modbus RTU Slave
Slave No.
xxh
Communication Example
Read 2 words starting at data register D1710.
D1710 → (1710 – 0) + 400001 = 401711
Modbus address: 401711
Purpose
Extract lower 5 digits → 1711
1711 – 1 = 1710 = 6AEh
Communication frame address: 06AEh
Slave No. 8
Condition
D1710 data: 1234h
D1711 data: 5678h
Modbus RTU Mode
Request from Modbus RTU Master
ACK Reply from Modbus RTU Slave
NAK Reply from Modbus RTU Slave
Function Code
Address
03h / 04h
xxxxh
Function Code
Quantity of Data
03h / 04h
xxh
Function Code
Error Code
83h / 84h
xxh
08 03 06AE 0002 (CRC)
08 03 04 12 34 56 78 (CRC)
08 83 xx (CRC)
FC6A S
M
S
A
ERIES
ICRO
MART
LL
No. of Words
xxxxh
First High Byte
xxh
-
-O
T
C
IN
NE
YPE
OMMUNICATION
6: M
ODBUS
First Low Byte
xxh
M
FC9Y-B1730
ANUAL
C
OMMUNICATION
Last Low Byte
xxh
6-13