IDEC FC6A-C16K1CE Communications Manual page 92

Fc6a series microsmart all-in-one type
Hide thumbs Also See for FC6A-C16K1CE:
Table of Contents

Advertisement

5: U
C
SER
OMMUNICATION
Multi-byte start delimiter
First two bytes can be configured as a multi-byte start delimiter. The incoming data is processed according to the receive format
only when the first two bytes of the incoming data match the start delimiter. Therefore, only the incoming data sent to slave
station 1 is processed. No extra ladder programming is needed to check the slave station number.
STX
"1"
(02h)
(31h)
(3xh) (3xh) (3xh) (3xh)
Start
Delimiter
Designating Constant as End Delimiter
An end delimiter can be programmed at the end of the receive format of a RXD instruction; the FC6A Series MicroSmart will
recognize the end of valid communication, although RXD instructions without an end delimiter can also be executed.
When a constant value is designated at the end of source device S1, the one-byte data serves as an end delimiter to end the
processing of the received data. If data bits are set to 7 bits, the end delimiters will be between 00h and 7Fh. If data bits are set
to 8 bits, the end delimiters will be between 00h and FFh. Constant values are entered in character or hexadecimal notation into
the source data. When using the same RXD instruction repeatedly in a user program, assign different end delimiters for each RXD
instruction.
If a character in incoming data matches the end delimiter, the RXD instruction ends receiving data at this point and starts
subsequent receive processing as specified. Even if a character matches the end delimiter at a position earlier than expected, the
RXD instruction ends receiving data there.
If a BCC code is included in the receive format of a RXD instruction, an end delimiter can be positioned immediately before or after
the BCC code. If a data register or skip is designated between the BCC and end delimiter, correct receiving is not ensured.
When a RXD instruction without an end delimiter is executed, data receiving ends when the specified bytes of data in the receive
format, such as data registers and skips, have been received. In addition, data receiving also ends when the interval between
incoming data characters exceeds the receive timeout value specified in the Communication Parameters dialog box whether the
RXD has an end delimiter or not. The character interval timer is started when the first character of incoming communication is
received and restarted each time the next character is received. When a character is not received within a predetermined period of
time, timeout occurs and the RXD ends data receive operation.
Example:
(1) When a RXD instruction without an end delimiter is executed
Incoming Data
"0"
"1"
"2"
(30h)
(31h)
(32h)
Total of received characters
The incoming data is divided, converted, and stored to data registers according to the receive format.
Receive operation is completed when the total characters programmed in RXD are received.
(2) When a RXD instruction with end delimiter ETX (03h) and without BCC is executed
Incoming Data
"1"
"2"
"3"
(31h)
(32h)
(33h)
End of receiving data
The incoming data is divided, converted, and stored to data registers according to the receive format.
The end delimiter is not stored to a data register.
Any data arriving after the end delimiter is discarded.
5-16
I
NSTRUCTIONS
CR
(13h)
Stored to D1
End
Delimiter
When D100 is designated
as the first data register
"3"
(33h)
When D100 is designated
as the first data register
ETX
(03h)
End Delimiter
FC6A S
M
S
A
ERIES
ICRO
MART
-
-O
T
C
LL
IN
NE
YPE
OMMUNICATION
D100
**** h
D101
**** h
**** h
D100+n
**** h
D100
**** h
D101
D100+n
**** h
M
FC9Y-B1730
ANUAL